Fix it
Not reporting to monitoring
Comms fail, line fault, or the monitoring centre isn't getting signals.
Quick fix
- Ring the monitoring centre and ask what they're seeing (or not) from the account.
- Old phone line dialler? NBN probably killed it. The panel needs an IP or 4G communicator.
- IP panel: check the network cable, link light and that the panel has an IP address.
- 4G: check signal strength, antenna and that the SIM's active.
- Send a test and confirm it's received before you leave.
Draft. Not yet checked on site. Confirm against the manual. Report an error
What the panel's telling you
- Ness / Bosch: LINE icon = phone line fault or failed to communicate.
- Bosch Solution 2000/3000: hold 5 for three seconds for fault analysis. Look for communication fail.
- Inner Range Inception: ALARMS LED red = alarms queued with no valid reporting path. Check the monitoring account and network settings.
- Ness D8xCEL: CELL showing low signal (under 5), 00 or noCELL means antenna, interference or SIM.
- Risco: GSM signal shows 0–5.
Common causes
- NBN connection with an old PSTN dialler.
- Router replaced, so the panel lost its IP or port settings.
- SIM expired or deactivated.
- Antenna not fitted, or inside a metal cabinet.