Home › Fix it › Zone won't seal
Fix it

Zone won't seal

Zone open or tampered with nobody there. Detector, cable or EOL setting?

Quick fix

  1. Walk the area. Open window, door not latched, blind or heater moving in front of a PIR.
  2. Lid on the detector? Tamper closed?
  3. Detector LED stays on with no movement = the detector's triggering, not the wiring.
  4. Fit a spare EOL straight across the zone terminals at the panel. Seals = fault's out in the cable or detector. Doesn't seal = check the panel's EOL setting.
  5. Meter the zone pair (disconnected, detector sealed). You should read the EOL value.

Draft. Not yet checked on site. Confirm against the manual. Report an error

What your meter reading means

  • Matches the EOL: cable's fine. Detector or panel input.
  • Open: broken cable, loose terminal, missing or burnt resistor.
  • Near zero: short. Staple, crushed cable, water.
  • Some other value: wrong resistor, or the panel's set for a different EOL. Very common on takeovers.

Default EOL by panel

Panel Default EOL
Ness D8x / D16x 2k2 (changed at P129E)
Bosch Solution 2000/3000 Split 3k3 / 6k8 (location 266)
Inner Range Inception 2k2 + 2k2 or 2k2 + 6k8
Inner Range Integriti 2k2 / 2k2 recommended (sealed 2k2, alarm 4k4)
Tecom Challenger 10k
Risco LightSYS Plus 2k2 (DEOL 2k2 / 2k2)

Inputs reading back to front

On Inner Range, if sealed and alarm are swapped, it's either the EOL wiring or the input needs Swap Active & Secure (or swap alarm and seal for N/O contacts).

Don't bypass a zone and walk away without telling the customer in writing that it's out of action.

Still stuck? Ask TechMate

Checked Nov 2026 · Report an error