Keypad dead or blank
Keypad has no display, no beeps, or shows a bus or comms error.
Quick fix
- Is the panel alive? Check mains and battery at the panel first.
- Meter the keypad's + and 0V at the keypad. No 12 V = cable or panel output.
- Check the data wires at both ends. Swapped data lines are common after a keypad swap.
- Check the keypad's address. Two keypads on the same address will fight.
- Re-enrol. Some panels need the keypad learnt again after it's replaced.
Draft. Not yet checked on site. Confirm against the manual. Report an error
Wiring limits
| Panel | Keypad bus |
|---|---|
| Ness D8x / D16x | +12V, CLK, DAT, COM. Up to 3 keypads, 100 m total |
| Bosch Solution 2000/3000 | Up to 4 codepads, addressed by DIP switch |
| Risco LightSYS Plus | Red +12, black 0V, yellow/green data. 300 m per leg |
| Paradox EVO | 4-wire combus, 914 m total. Only LCD/Grafica keypads can program |
After replacing a keypad
- Hills Reliance XR: after defaulting, re-enrol keypads by holding the learn button on the board for about 2 seconds.
- Interlogix NX: enter and exit program mode. The panel enrols every keypad and module automatically (about 12 seconds).