Fix it
Mains fault
MAINS light on, keypad beeping. Usually the plug pack or power point.
Quick fix
- Ask what changed. Power outage, sparky on site, cupboard tidied? It's usually been unplugged or switched off.
- Prove the power point is live and switched on. Check the RCD at the switchboard.
- Meter the AC at the panel's AC terminals. Near zero = dead plug pack or broken cable.
- Check the cable run for staples, crush points and loose screw terminals.
- Voltage good at the terminals but still faulting? Check the panel's AC fuse, then suspect the board.
Draft. Not yet checked on site. Confirm against the manual. Report an error
Why it matters
The panel's on battery and it'll go flat. Once the battery drops low enough the panel shuts down.
Expected plug pack voltage
| Panel | Supply |
|---|---|
| Bosch Solution 2000/3000 | 18 VAC |
| Ness D8x / D16x | 17 VAC, 1.4 A min |
| Paradox EVO | 16.5 VAC, 20 VA min (40 VA for more power) |
| Inner Range Inception | 18–24 V DC (24 V 2.5 A pack supplied). AC fail shows below 16.5 V |
| Risco LightSYS Plus | 14.4 V DC adaptor, permanently wired through the fused terminal block |
Expect a little higher than the rating with light load.
After it's fixed
- The battery's been working hard. If low battery hangs around, see Low battery.
- Clear the memory/alarm log so the customer isn't staring at an old fault.
Use the manufacturer's plug pack. Wrong voltage, or DC on an AC input, can kill the board or stop charging. Leave 240 V work to a licensed sparky.