Home › Inner Range › Inner Range Integriti (IAC)
Inner Range · Integrated access controller

Inner Range Integriti (IAC)

Defaulting links, LAN rules and status LEDs.

Quick fix

  1. Reset installer code: power down (AC and battery), short IN1, power up, wait for the Prompt LED to flash, briefly short OK.
  2. Full default: same, with IN1 and IN2 shorted. Wipes all programming.
  3. Status 1/2 alternate flashing = normal. Give it 60 seconds after power-up.
  4. LAN fault? Meter A to B. 470 Ω or less = short, or an old Concept module with its termination link still in.
  5. EOL: 2k2/2k2 recommended (sealed 2k2, alarm 4k4).

Draft. Not yet checked on site. Confirm against the manual. Report an error

LAN rules

  • Twisted pair (Cat5/5e or two-pair). A and B in parallel, NEG to every module.
  • Shielded cable in noisy spots, shield earthed at one end only.
  • Never join two + supplies. Don't run locks or detectors off LAN power. Use DET+ / DET−.
  • Pull the termination links out of old Concept 3000/4000 modules on an Integriti LAN.

Status and fault LEDs

LEDs Means
Status 1/2 alternating Normal
Status both on, Fault both off Booting with no SD card
Status 2 off, Fault 1 flashing Database error
Status 1 and 2 on, Fault 2 flashing Review error
Module RX/TX both on Module not addressed
Module RX/TX both flashing Module number too high
Specs at a glance
Power
13.75 V from an Integriti Smart PSU. Low voltage below 11 V
Idle draw
150 mA + 35 mA per lock relay
LAN
Self-terminating. 1500 m per module. No isolators: < 2000 m and < 64 modules
LAN voltage
11–14 V DC + to −
Software
Integriti Pro, Express (one controller), CS
Manuals & downloads

Related

Module or device offlineLocked out of an alarm panelZone won't seal
Still stuck? Ask TechMate

Checked Nov 2026 · Report an error