Paradox · Alarm panel
Paradox EVO48 / EVO192
Combus, battery testing, programming and first power-up.
Quick fix
- Into programming: hold
0, enter the installer code, then the 4-digit section. LCD or Grafica keypad only. LED keypads can't program. - Restart without powering down: hold the reset button 2 seconds.
- Clock Loss and Bell Absent on first power-up are normal. Set the clock, check the siren.
- Adding a module? Remove AC and battery first.
- Battery trouble: tested every 60 s. Trouble at 10.5 V with no AC. Reversed leads blow the battery fuse.
Draft. Not yet checked on site. Confirm against the manual. Report an error
Combus in noisy spots
Use shielded cable. Ground the shield at the panel end only and leave the far end floating.
Specs at a glance
- Transformer
- 16.5 VAC, 20 VA min (40 VA for more power)
- Battery
- 12 V 7 Ah min. Charge 350 or 850 mA
- AUX
- 700 mA (shuts down over 1.1 A). BELL + AUX < 2 A
- Combus
- 4-wire, star or daisy chain, 914 m total
- Modules
- EVO48: 127. EVO192: 254
- 1k EOL
- Section 3033 option 7 (off by default)
- Zone doubling (ATZ)
- Section 3033 option 8