Home › Tecom › Tecom Challenger / ChallengerPlus
Tecom · Alarm & access

Tecom Challenger / ChallengerPlus

Install menu, defaults, EOL and LAN poll errors.

Quick fix

  1. Install menu: user menu option 19. All areas must be disarmed.
  2. Factory defaults: Install menu option 14.
  3. Lost installer PIN: briefly fit test link 1 on the board, then remove it.
  4. EOL: default 10k (EOL code 0).
  5. LAN faults: check poll errors, then reset the counts once it's clean.

Draft. Not yet checked on site. Confirm against the manual. Report an error

Gotchas

  • A panel left unpowered for more than two weeks may need defaulting.
  • Some setup has to be done on an LCD RAS before management software can connect.
  • Check batteries every three months on these sites.
Specs at a glance
LANs
Two RS-485 LANs
Battery
12 V SLA. 8 A slow-blow fuse in each battery + lead
Software
CTPlus, TecomC4, Forcefield, Security Commander