Tecom · Alarm & access
Tecom Challenger / ChallengerPlus
Install menu, defaults, EOL and LAN poll errors.
Quick fix
- Install menu: user menu option 19. All areas must be disarmed.
- Factory defaults: Install menu option 14.
- Lost installer PIN: briefly fit test link 1 on the board, then remove it.
- EOL: default 10k (EOL code 0).
- LAN faults: check poll errors, then reset the counts once it's clean.
Draft. Not yet checked on site. Confirm against the manual. Report an error
Gotchas
- A panel left unpowered for more than two weeks may need defaulting.
- Some setup has to be done on an LCD RAS before management software can connect.
- Check batteries every three months on these sites.
Specs at a glance
- LANs
- Two RS-485 LANs
- Battery
- 12 V SLA. 8 A slow-blow fuse in each battery + lead
- Software
- CTPlus, TecomC4, Forcefield, Security Commander