Home › Inner Range › Inner Range Inception
Inner Range · Alarm & access

Inner Range Inception

Web-based controller. Logins, resets, LEDs and LAN wiring.

Quick fix

  1. Get in: SkyTunnel by serial number, or join its Wi-Fi (named after the serial) and browse to inception.local.
  2. Lost the login: 5 quick presses of the reset button = installer reset only (keeps programming).
  3. Full factory default: hold the reset button 5 seconds. Beep at the start, higher beep when done.
  4. SYSTEM LED red = a power output is shorted. Unplug VOUT, LAN and reader, then reconnect one at a time.
  5. ALARMS LED red = alarms queued with no reporting path. Check the monitoring and network settings.

Draft. Not yet checked on site. Confirm against the manual. Report an error

Status LEDs

LED Means
POWER solid green Normal. Fast flash = DC IN out of range
SYSTEM flashing green Running. Solid red = output shorted
ETHERNET green Cable connected and IP assigned
SKYTUNNEL green Cloud connected
ALARMS red Alarms waiting to send
WIFI flashing Adapter present but not connected

Gotchas

  • Sirens after leaving service mode: armed areas with unsealed or tampered inputs, or a module tamper.
  • Inputs back to front: check EOL wiring, or set Swap Active & Secure on the input.
  • Wrong event times: check date, time and NTP.
  • Browser reset (System › Backup/Restore) keeps the logs; the button reset doesn't.
  • Replace the battery every 3 years typically, 5 at most.
Specs at a glance
Power
18–24 V DC (24 V 2.5 A pack). AC fail below 16.5 V
Battery
12 V 7–18 Ah. Low at 11.0 V, cuts out at 10.4 V
Standby (light load)
7 Ah ≈ 16 h. 18 Ah ≈ 40 h
Inputs
8 onboard. Default EOL 2k2+2k2 or 2k2+6k8
LAN
1500 m per module, 2000 m total, 250 modules
Readers
1000 m total, up to 8
Manuals & downloads

Related

Module or device offlineSiren won't stopZone won't sealLocked out of an alarm panel
Still stuck? Ask TechMate

Checked Nov 2026 · Report an error