Inner Range · Alarm & access
Inner Range Inception
Web-based controller. Logins, resets, LEDs and LAN wiring.
Quick fix
- Get in: SkyTunnel by serial number, or join its Wi-Fi (named after the serial) and browse to
inception.local. - Lost the login: 5 quick presses of the reset button = installer reset only (keeps programming).
- Full factory default: hold the reset button 5 seconds. Beep at the start, higher beep when done.
- SYSTEM LED red = a power output is shorted. Unplug VOUT, LAN and reader, then reconnect one at a time.
- ALARMS LED red = alarms queued with no reporting path. Check the monitoring and network settings.
Draft. Not yet checked on site. Confirm against the manual. Report an error
Status LEDs
| LED | Means |
|---|---|
| POWER solid green | Normal. Fast flash = DC IN out of range |
| SYSTEM flashing green | Running. Solid red = output shorted |
| ETHERNET green | Cable connected and IP assigned |
| SKYTUNNEL green | Cloud connected |
| ALARMS red | Alarms waiting to send |
| WIFI flashing | Adapter present but not connected |
Gotchas
- Sirens after leaving service mode: armed areas with unsealed or tampered inputs, or a module tamper.
- Inputs back to front: check EOL wiring, or set Swap Active & Secure on the input.
- Wrong event times: check date, time and NTP.
- Browser reset (System › Backup/Restore) keeps the logs; the button reset doesn't.
- Replace the battery every 3 years typically, 5 at most.
Specs at a glance
- Power
- 18–24 V DC (24 V 2.5 A pack). AC fail below 16.5 V
- Battery
- 12 V 7–18 Ah. Low at 11.0 V, cuts out at 10.4 V
- Standby (light load)
- 7 Ah ≈ 16 h. 18 Ah ≈ 40 h
- Inputs
- 8 onboard. Default EOL 2k2+2k2 or 2k2+6k8
- LAN
- 1500 m per module, 2000 m total, 250 modules
- Readers
- 1000 m total, up to 8